Putting into use
■ Open valves carefully and chek installation for
leakage.
■ If the sleep mode of the counter is enabled
(Display: SLEEP 1), then it must be deacti-
vated by longer pressing the button (>5s).
■ While the system is operating, check whether
the volume display advances and the temper-
atures displayed correspond with the actual
temperatures (see the display overview).
■ Wait for the temperature display to be updated
(1-2 sec).
■ Secure meter with the enclosed sealing mate-
rial against unauthorised removal.
■ Fill in the putting into use report in accordance
with PTB-Directive TR K9.
Mounting in existing immersion sleeves:
The device C5 can be put into use in connection
with existing immersion sleeves in accordance
with the article „Putting into use of MID homolo-
gated temperature sensors” released in the PTB
notications 119 (2009), vol. 6.
Based on current information, the regulation
has a period of validity until 30.10.2016. For the
identication and marking of the usable existing
immersion sleeves in connection with the C5
device, an identication and marking set can be
delivered from our company.
Consumer
Symmetrical sensor installation for zelsius
®
C5-IUF with the return
sensor integrated in the measuring capsule
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-IUF
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-IUF with the return
sensor integrated in the measuring capsule
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-IUF
Supply
Return